The reason why the cooling thermostat Chiller suddenly fails to start

If there are any unexpected situations during the use of the cooling thermostat Chiller, it is important to promptly identify the specific reasons before resolving them, in order to effectively address various issues. For example, what is the reason why the cooling thermostat Chiller suddenly fails to start during operation?
One、 The reason why the cooling thermostat Chiller cannot start
1. The main reason is that during the operation of the system, the pressure at the equipment inlet is low, which cannot meet the basic operating conditions, leading to the problem of not being able to start.
2. According to the instructions for the configuration of the refrigeration thermostat Chiller, it can be understood that it is mainly caused by the idle water pump and other reasons. As long as the air in each system of the refrigeration thermostat Chiller is released, it can meet the suitable operating environment and achieve the purpose of starting the refrigeration thermostat Chiller.
3. The issue of stress. After experiencing varying degrees of startup difficulties, it is necessary to complete the maintenance of the refrigeration thermostat Chiller according to actual needs.
4. To ensure smooth operation, it is necessary to effectively control the inlet and outlet of the water pump during the use of the refrigeration thermostat Chiller. As the air is continuously eliminated, any malfunctions that cannot be started can be resolved.
Two、 Handling methods for encountering high-voltage faults
1. Due to insufficient cooling water flow, the rated water flow cannot be reached. The main manifestation is that the pressure difference between the inlet and outlet water of the unit decreases and the temperature difference increases. The reason for insufficient water flow is due to a lack of water or air in the system. The solution is to install an exhaust valve at a high position in the pipeline for exhaust; If the pipeline filter is blocked or too fine, and the permeability is limited, a suitable filter should be selected and the filter screen should be cleaned regularly; The selection of water pumps is relatively small and not compatible with the system. Excessive refrigerant charge.
2. This situation usually occurs after maintenance, manifested as high suction and exhaust pressure, balance pressure, and high operating current of the compressor. It should be deflated under rated operating conditions based on suction and exhaust pressure, balance pressure, and operating current until normal, so it is still necessary to regularly check.
Related recommendations
-
How to choose the lubricant for the injection molding machine?
1418The injection molding machine cooling system lubricating oil needs to pay attention to the type of compressor when selecting. The compressor has three types: piston type, screw type and centrifugal type. The first two kinds of lubricating oil are ...
View details -
Introduction of LNEYA Heating Cooling Circulator Thermostat
1218Nowadays, the problem that plagues the pharmaceutical and chemical industry is the problem of temperature control. With the increasing industry demand and temperature control requirements of the pharmaceutical and chemical industry, the use of hea...
View details -
Low temperature refrigeration unit maintenance inspection
1128Low-temperature refrigeration units usually need to do a maintenance. After the maintenance is done, it is not easy to fail, and there will be more markets. If it is not easy to fail, it will not stop working, which is equivalent to saving the com...
View details -
Temperature sensor for ultra-low temperature refrigerator
1181Ultra-low temperature refrigerators are used in refrigeration equipment. They are generally used in refrigeration equipment below -60 ° C. They are used under some special conditions under low temperature conditions. Temperature control is very im...
View details