  • Product Description
TES
Temperature control range:-45°C ~ 250°C ;Power range:2.5kW~25kW;Temperature control accuracy:±0.3°C
Chip-Specific High and Low Temperature Test Boxes In the manufacture of semiconductor electronic components for harsh environments, the IC packaging assembly and engineering and production testing phases include electronic thermal testing at temperatures (-85 °C to +200 °C) and other environments. Test the simulation. Once put into practical use, these semiconductor devices and electronic products can be exposed to extreme environmental conditions to meet demanding military and telecommunications reliability standards.


Model TES-4525 TES-4555 TES-45A10 TES-45A15 TES-45A25
TES-4525W TES-4555W TES-45A10W TES-45A25W TES-45A25W
Temp. Range -45℃~250℃ -45℃~250℃ -45℃~250℃ -45℃~250℃ -45℃~250℃
Heating Power 3.0kW 5.5kW 10kW 15kW 25kW
refrigerating output 250℃ 2.5kW 5.5kW 10kW 15kW 25kW
100℃ 3.0kW 5.5kW 10kW 15kW 25kW
20℃ 2.5kW 5.5kW 10kW 15kW 25kW
0℃ 2.5kW 5kW 10kW 15kW 25kW
-20℃ 1kW 2.9kW 6kW 11kW 16kW
-40℃ 0.3kW 0.9kW 2kW 3.8kW 5.3kW
Temp. control accuracy of heat conduction medium ±0.3℃ ±0.3℃ ±0.3℃ ±0.3℃ ±0.3℃
System pressure display The pressure of the refrigeration system is realized by the pointer type pressure gauge (high-pressure and low-pressure).
The circulation system pressure is displayed on the touch screen by pressure sensor detection.
controller Siemens PLC, Fuzzy PID Control algorithm with Cascade Control algorithm
Temp. control Temperature Control Mode for outlet of Heat conduction medium;
External temperature sensor: (PT100 or 4~20mA or communication given) control mode (cascade control)
Programmable 5 procedures can be developed, and each program can be composed of 40 steps
Communicating protocol Ethernet Interface TCP/IP Protocol
Internal temp. feedback of equipment Equipment heat-conducting medium outlet temperature, medium inlet temperature, refrigeration system condensation temperature, ambient temperature, compressor suction temperature, cooling water temperature (configuration of water-cooling equipment)
External access temp. feedback PT100 or 4~20mA or communication given
String-level control The temperature difference between the outlet temperature and the external temperature sensor can be set and controlled;
Temp. difference control function The temperature difference between the inlet temperature and the outlet temperature of the equipment can be set to be controlled (to protect the safety of the system).
Closed-cycle system The whole system is a completely closed system with no oil mist at high temperature and no water in the air at low temperature. The system will not increase the pressure due to high temperature and automatically replenish the heat conduction medium at low temperature.
Heat The maximum heating output power of the system (according to each model);
The heater has triple protection and independent temperature limiter to ensure the safety of heating system;
The power is more than 10kW and the voltage regulator is adopted, and the heating power output control is controlled by 4-20mA linear control.
Aefrigerating capacity It refers to the ability to carry away heat at different temperatures (in the ideal state). The actual working conditions need to be considered for environmental heat dissipation. Please enlarge it properly and do well the thermal insulation measures.
Circulation pump flow, pressure max Magnetic drive pump
25L/min2.5bar 50L/min2.5bar 50L/min2.5bar 110L/min2.5bar 150L/min2.5bar
Compression engine Tekokang,France Emerson Emerson / Danvers Emerson / Danvers Emerson / Danvers
Evaporimeter Plate Heat Exchanger
Refrigeration Accessory Danfoss / Emerson fittings (dry filters, oil separators, high and low pressure protectors, expansion valves)
Operation panel LNEYA custom 7-inch color touch screen, temperature curve display\ EXCEL data export
Safe guarding With self-diagnosis function; phase sequence phase breaker, freezer overload protection; high-voltage pressure switch, overload relay, thermal protection device and other safety protection functions.
Cryogen R-404A / R507C
Interface size ZG1/2 ZG3/4 ZG3/4 ZG1 DN32 PN10 RF
Shape size (Water-cooled type)cm 45*70*160 55*70*175 65*85*185 80*120*185 100*150*185
Air-cooled type It adopts copper tube aluminum fin condensation method, upper air outlet type, and the condensation fan adopts German EBM axial flow fan.
Water-cooled type W Type W is water cooled
Water-cooled Condenser Casing heat exchanger (Paris / Shen’s)
Cooling water quantity at 25℃ 1.1m3/h 1.5m3/h 2.6m3/h 3.6m3/h 7m3/h
Source 380V50HZ 6kW max 220V 9kW max 16kW max 23kW max 36kW max
Source Customizable 460V 60HZN 220V 60HZ three-phase
Shell material Cold rolled sheet spray (Standard Colour 7035)
Isolation explosion proof Customizable isolation explosion proof (EXdIIBT4);
Installation License No. of Wuxi Guanzi Explosion-proof Product: PCEC-2017-B025
Barotropic explosion protection A custom positive pressure explosion-proof (EXPXdmbIICT4) positive pressure system must be a water-cooled device;
Installation License No. of Wuxi Guanzi Explosion-proof Product: PCEC-2017-B025



Related Products
  • SLJ -110℃~-150℃

    SLJ -110℃~-150℃

    January 11, 2018Temperature ranges from - 5 ~ - 150 ℃, can meet different temperature; Adopt environmental protection refrigerants; Famous brand semi-closed piston compressor, semi-closed bipolar piston compressor, semi-hermetic screw compressor, main brand are BOCK.view
  • Single Fluid Heat Transfer System SR

    Single Fluid Heat Transfer System SR

    April 10, 2018Working temperature range from -25℃to 200℃, other temperature range need to set to the widest temperature range(-50℃to 250℃) Centralized control of 2~20 reactors, each reactor's and jacket temperature can be set independently. One system control multipleview
  • Reactor Temperature System ZLF

    Reactor Temperature System ZLF

    April 10, 2018A set of cooling heat exchanger, heat exchanger, through proportional adjusting valve control cold heat into the heat exchanger, then through the uniform medium input to the reactor jacketed to do heat exchange and temp. Control, system has inside expansiview
Leave a Message Email Us

we will contact you within 24 hours.

products
Contact US
Tel: + 86 18751545184
E-mail: sales@cnzlj.com
Add: No.203, Hongyun Road, Hongshan Street, Optoelectronics Park, Xinwu District, Wuxi City, Jiangsu Province, China
code chat