What are the refrigerants for the 120-degree ultra-low temperature freezer?
The refrigerants of different ultra-low temperature freezer manufacturers are different. The refrigerants commonly used in LNEYA refrigeration equipment are R404, R22, etc. So, what is the difference between the two-120-degree ultra-low temperature freezer refrigerant?
Since the saturation pressure of R404A is higher than R22, the design pressure of the pressure vessel in the system should be changed to ensure safety. Such as liquid storage and gas-liquid separators. At the same time, the set values of the safety valve and fusible plug installed on the system components will also change. Since the gas density of R404A is about 50% larger than that of R22 under the same exhaust gas amount, the pipe diameter selected is larger than R22 when piping design using R404A refrigerant.
For the same compressor, the current of the R40A in the -120 degree ultra-low temperature freezer is greater than R22, so the wire diameter of the AC contactor, thermal relay and cable of the compressor should be adjusted. In terms of system protection, the high pressure switch setting is adjusted from the original 2.45 MPa to 2.7 MPa. The exhaust pressure of the R404A refrigerant is about 1.2 times that of R22, and the mass flow rate is about 1.5 times that of R22. The exhaust flow rate increases and the resistance increases. In general, the heat transfer capacity of the condenser is increased by 20% to 30% compared to R22.
The saturation pressure of R404A and R22 is different at the same temperature, so the action mechanism of the -120 degree ultra-low temperature freezer R404A thermal expansion valve is different from that of R22. At the same time, because the R404A refrigerant and lubricating oil have different compatibility with the sealing material, the expansion valve sealing material should also be changed accordingly. Therefore, the R404A special expansion valve should be selected in the selection of the thermal expansion valve. Since the saturation pressure of 404A is different from that of R22, the air tightness test pressure is greater than R22. At the same time, the vacuum degree of the system is higher than R22, and the water content is lower than R22. The refrigerant should be charged in liquid form during charging to prevent changes in the R404A configuration.
The refrigerant R404A used in the 120 degree ultra-low temperature freezer is a non-azeotropic mixture. The concentration of the non-azeotropic mixture changes with temperature and pressure, which brings certain difficulties to the production, commissioning and maintenance of the refrigeration system. The heat transfer performance of the system will also have a certain impact, especially when the refrigerant leaks, the system refrigerant needs to be completely drained and replaced, so as to ensure the proportion of each mixed component, and also achieve the design cooling effect, otherwise it will get worse. .
The refrigerant of the -120 degree ultra-low temperature freezer should be selected according to the corresponding equipment. LNEYA selects the corresponding environmentally friendly refrigerant refrigerant, which is more in line with the development of the environmental protection theme of the contemporary era.

Related recommendations
-
Four Key Points of Water Cooled Chiller Installation
889The installation of water-cooled chiller can be carried out from four aspects: first, the installation of chiller, then the installation of water pipe, water pipe cleaning and equipment insulation. Do not underestimate the installation of this par...
View details -
2018 CIPM China | You have an invitation to the exhibition from LNEYA
1025The 56th (Fall 2018) National Pharmaceutical Machinery and China International Pharmaceutical Machinery Expo will be held from November 5th to November 7th, 2018 at Wuhan International Expo Center. As one of the professional communication platfor...
View details -
Description of driver chip power supply in chip test temperature control system
747The chip test temperature control system is mainly for the cold heat source test equipment for various drive chips. Before the operation of the Wuxi Guanya chip test temperature control system, the user needs to know the power of the drive chip. I...
View details -
How does the cooling and heating circulator equipment control the temperature of the jacket glass re
715The cooling and heating circulator equipment is often equipped with a reaction kettle for temperature control, so how to connect and control the temperature? 1. Circular jacket inlet and outlet interface We mainly use flange interfaces for the in...
View details