Detailed Operating Instructions of Industrial Chiller
The installation procedures of water
chiller include:
1. During installation, please check
whether the machine is damaged and select a suitable place for installation and
future maintenance. The site for installing the unit must be the floor or
installation pad, with a levelness within 6.4mm, and can bear the operating
weight of the unit.
2. The chiller shall be placed in the
machine room with room temperature of 4.4-43.3 ℃, and there shall be enough space around and above the unit for
daily maintenance.
3. At one end of the unit, a pipe
extraction space for cleaning the condenser tube bundle shall be reserved, and
door holes or other holes at appropriate positions can also be used.
4. Select water pipes with appropriate pipe
diameter, cooling system and cold water system when the unit operates at
maximum power, and connect them correctly.
5. For ordinary applications, the water
flow velocity through the evaporator and condenser is allowed to be between
1.0-3.6m/s.
6. The water flow shall be stable under any
load.
7. All cooling water pipes shall be
designed and installed according to the conventional method. The chilled water
pump shall be located on the inlet pipe of the chiller to ensure the positive
pressure and flow in the unit. When piping, damping pipes shall be set to
ensure proper elasticity, and prevent the water in the evaporator from being
drained when the water pump stops.
8. The pipeline shall be firmly supported
independent of the chiller to avoid stress on the components of the chiller.
9. In order to reduce noise and vibration,
it is better to install vibration isolator on the pipeline.
10. In order to use the chiller
economically and effectively, it is recommended to invite water treatment
experts to analyze the water supply quality of evaporator and condenser. Poor
water quality will cause scale, affect heat transfer, or produce corrosion
precipitation, affect the performance of the unit and increase operation and
maintenance costs.
11. Generally speaking, proper water
treatment and regular cleaning can maintain its good performance.
12. Please install a filter at the inlet of
the water pipe and clean it regularly.
13. After leak test, all nozzle openings
must be treated with rust prevention.
14. In order to facilitate daily
maintenance, the user can take some (or all) of the following measures: the
pressure gauge and stop valve with cock can be installed on the inlet and
outlet pipes of cooling water and chilled water, close to the chiller as far as
possible;
Lifting rails and beams can be erected
above the equipment to facilitate maintenance.
Related recommendations
-
Analysis of Advantages and Disadvantages of Screw Water Chiller
1242Compared with other types of chillers, the overall energy consumption of high-quality screw water chiller is relatively small. Because the production technology of screw water chiller is more advanced and less energy is used, the equipment can qui...
View details -
Temperature control range and accuracy of high and low temperature tester
1021The temperature control accuracy of heat transfer oil medium of the high and low temperature tester used for component testing is plus or minus 0.5 ℃, which solves the problem of temperature control lag in electronic components. Main advantages of...
View details -
2018 CIPM China | You have an invitation to the exhibition from LNEYA
1198The 56th (Fall 2018) National Pharmaceutical Machinery and China International Pharmaceutical Machinery Expo will be held from November 5th to November 7th, 2018 at Wuhan International Expo Center. As one of the professional communication platfor...
View details -
Accurate temperature control for battery testing to improve the performance of electric vehicles
829Electric vehicles (EVs) have completely transformed the automotive industry, providing a more sustainable and energy-efficient mode of transportation. One of the basic components of electric vehicles is their rechargeable battery. Electric v...
View details