How to prevent the freezing pressure of the bearing quick freezing box from being too low?
In the refrigeration system of the bearing blast chiller, if the condenser installation is not in the enclosed space, the system’s exhaust pressure (condensation pressure) tends to be lower in winter (or low temperature), which is often more common in the north. For bearing blasters, this is also the case for other equipment.
The low condensing pressure of the bearing quick freezing box will make the expansion valve unable to obtain sufficient pressure drop at both ends, and it is difficult to supply the appropriate refrigerant to the evaporator. On the one hand, the cooling capacity of the refrigeration system will not meet the requirements, and the system will also be made. Frequent low-voltage alarms and other faults.
To this end, we can deal with the method of exhaust pressure controller. When the intermittent operation of the fan is simple and easy to use, and the technology is mature, the controller used is a pressure controller. This pressure controller can control the intermittent start and stop of the fan. When the pressure is too low, turn off the fan. When the pressure is too high, turn on the fan. Generally, on a small-capacity unit, use two or more fans, one of which is normally open, and the other fans are pressure controlled. The controller controls the start or stop of the fan by the level of the condensing pressure.
It is also possible to use a pneumatic control device to utilize a high-pressure refrigerant-driven piston-type damper. This control device can operate as a stable exhaust pressure as the fan speed controller; the main reason is that the inlet pressure of the expansion valve does not resemble a fan. Intermittent operation produces large fluctuations, and the louver device can be installed either at the air inlet or at the air outlet.
In addition, the condenser overflow device can also be used to increase the condensing pressure of the system by using excess refrigerant, and the condenser overflow device is used for warming or low temperature environment, and the large flow refrigerant is taken from the liquid storage device. It is sent to the condenser, and the excess refrigerant is used to increase the condensing pressure of the system, thereby avoiding the failure of the condensing pressure being too low at low temperatures.
LNEYA’s methods to prevent the bearing chiller from condensing too low pressure are still relatively high, and users can try it according to their own needs.
Related recommendations
-
How to replace the scroll compressor of the impact tester model?
2127In terms of different impact tester models, the configuration is also somewhat different. Among them, special care should be taken when replacing the scroll is a compressor. If the replacement is not noticed, the impact tester cannot be used. The ...
View details -
The main purpose of the ethylene glycol chiller for the heating and cooling unit of the reactor
1796The glycol chiller is suitable forhigh-purity metal, rare substance purification, laboratory environmentsimulation, magnetron sputtering, vacuum coating and other industries. Largecryogenic pump units can provide a cooling environment for labor...
View details -
Product Features of Fluid Heat Transfer Temperature Control System
1632The fluid heat transfer temperature control system is the refrigeration and heating device of the matching reactor reactor in the pharmaceutical chemical industry. So, what are the characteristics of the fluid heat transfer temperature control sys...
View details -
Refrigeration heating cycle device compressor precautions
1776The performance of the compressor in the refrigeration heating cycle device is very important. When choosing the compressor brand of LNEYA refrigeration and heating cycle device, the compressors of domestic and foreign brand manufacturers are spec...
View details
LNEYA Industrial Chillers Manufacturer Supplier










