SEARCH
Search the allChillersWater ChillerSUNDI series
Search
Hot Products
Thermoatats SUNDI Series/ TCU/KRY series/WTD seriesChillers LT series/ FL series/CDYL seriesAir Cooling Chiller Water Cooling Chiller
SEARCH
1.The standard design conditions are: chilled water:outlet water temperature 7 ° C, return water temperature 12 ° C; condensing temperature 40 ° C.
2.Due to continuous updating of product technology, the above data is subject to change without prior notice.
3.In addition to the listed product models, our company can customize non-standard units according to customer requirements.
Model FL-WS | 90 | 100 | 140 | 180 | 200 | 250 | 300 | 350 | 400 | 460 | 510 | 600 | 660 | 750 | 830 | 940 | |
Cooling capacity |
KW | 98 | 109 | 136 | 159 | 195 | 249 | 297 | 349 | 388 | 459 | 506 | 588 | 658 | 745 | 849 | 934 |
Kcal/hr *10³ |
85 | 98 | 117 | 137 | 168 | 214 | 255 | 300 | 334 | 395 | 435 | 506 | 566 | 641 | 731 | 803 | |
Power | 3N/380V/50HZ | ||||||||||||||||
Cooling input power |
KW | 18 | 23 | 30 | 36 | 44 | 51 | 65 | 77 | 85 | 100 | 110 | 127 | 140 | 157 | 198 | 213 |
Compressor | Form | semi-closed double screw compressor | |||||||||||||||
Heat control range |
0~25~37.5~50~62.5~75~87.5~100(12.5% segmentation control) | ||||||||||||||||
Chilled water |
Form | Dry, overflow or falling film heat exchanger | |||||||||||||||
Chilled water volume T/H |
15.5 | 18 | 23 | 27 | 33 | 42 | 51 | 60 | 67 | 79 | 87 | 101 | 113 | 128 | 146 | 160 | |
Water pressure drop KPa |
49 | 60 | 73 | ||||||||||||||
Connection size |
DN65 | DN80 | DN100 | DN125 | DN150 | ||||||||||||
cooling water |
Form | horizontal and tube sheel type | |||||||||||||||
cooling water volume T/H |
20 | 25 | 28 | 33 | 41 | 53 | 62 | 72 | 80 | 107 | 118 | 136 | 150 | 171 | 198 | 213 | |
Water pressure drop KPa |
45 | ||||||||||||||||
Connection size |
DN65 | DN80 | DN100 | DN125 | DN150 | ||||||||||||
Security device |
High and low voltage protection, anti-icing, heat release protection (double), safety valve, overload protection, under-phase, reverse phase, under voltage, over voltage, water flow protection, etc. |
||||||||||||||||
Refrigerant | Charge Kg |
20 | 23 | 30 | 35 | 44 | 48 | 55 | 58 | 61 | 75 | 85 | 90 | 115 | 133 | 155 | 165 |
Dimension | Length mm |
2500 | 2500 | 2585 | 2635 | 2635 | 3100 | 3130 | 3130 | 3135 | 3135 | 3135 | 3135 | 3275 | 3300 | 3300 | 3668 |
Width mm |
850 | 850 | 900 | 900 | 900 | 1100 | 1100 | 1100 | 1100 | 1100 | 1100 | 1100 | 1100 | 1100 | 1100 | 1100 | |
Height mm |
1300 | 1300 | 1335 | 1335 | 1428 | 1428 | 1570 | 1680 | 1776 | 1800 | 1800 | 2000 | 2020 | 2070 | 2100 | 2120 | |
Unit weight |
kg | 850 | 850 | 850 | 1050 | 1270 | 1430 | 1740 | 1850 | 2480 | 2600 | 2870 | 3200 | 3400 | 3600 | 3850 | 4345 |
Working weight |
kg | 900 | 900 | 900 | 1100 | 1420 | 1580 | 1890 | 2050 | 2580 | 2800 | 3120 | 3500 | 3700 | 3900 | 4150 | 4640 |
LT LJ CDLJ series etc. both water cooled and air cooled chiller type
Cooling Power 1.8kW to 60kW Conventional chillers can only cool at room temperature
Cooling power 0.35kW~0.9kW Power range 0.6kW
Cooling power 45KW Temperture accuracy ±0.5℃