Three Common Failures Of Air Cooled Screw Chiller
Three Common Failures Of Air Cooled Screw Chiller
1. Communication Failure:
Computer controller controls various modules by telecommunication lines and total interface board, so the main cause of communication failure is poor contact or break of communication lines, especially the interface oxidation and damp of the interface. Also, the failure of unit electronic board or total interface board, incorrect choice of address dial code switch and power failure can cause the communication failure.
2. Low Voltage Failure:
The low suction pressure of the compressor results in low pressure protection relay action. The suction pressure of the compressor reflects the evaporation pressure, whose the normal value should be 0.4~ 0.6mpa, and the protection value is set to 0.2mpa. Low suction pressure causes low return air volume and insufficient cooling capacity, resulting in waste of electrical energy and the heat dissipation of the motor of gas cooled compressor which is easy to damage the motor.
3. High Voltage Failure:
High exhaust pressure of compressor results in high voltage protection relay action. The compressor exhaust pressure reflects condensation pressure whose normal value should be 1.4~ 1.6mpa, and the protection value is set to 2.0mpa. If the pressure is too high for a long time, it will cause too large of the current of compressor, which is easy to burn the motor and damage the compressor exhaust valve disc.
Related recommendations
-
Won the “2021 High Quality Development Award”
1707On the afternoon of May 8, 2022, the 2020 Annual Summary and Commendation Conference was held in Hongshan Street, Wuxi City. Wuxi Guanya Constant Temperature Refrigeration Technology Co., Ltd. (LNEYA) won the "2020 Outstanding Contribution Award"...
View details -
The reason why the cooling water circulator needs the main water circulation
1251The supplement of the water cycle is directed to a water-cooled cooling water circulator, and the air-cooled cooling water circulator does not have this problem. The water-cooled cooling water circulator needs cooling water during normal operation...
View details -
Application of TCU in refrigeration and heating circulation system
1248In the process of pharmaceutical synthesis and fine chemical operation, we often encounter strong exothermic reactions such as oxidation reaction and acid-base neutralization. For these strong exothermic reactions, if the control is improper or th...
View details -
Analysis of Common Faults in New Energy Vehicle Power Battery Test System
996If the new energy vehicle power battery pack leaks, the general fault manifestation mode: the meter OK light does not light, the meter prompts to check the power system, the high voltage system leakage fault, disconnect the battery pack and the b...
View details