SR & ZLF series TCU Reactor Cooling Heating Temperature Control System
APPLICAZIONI
TCU temperature control system uses existing thermal energy (such as steam, cooling water and ultra-low temperature liquid - the "primary system") infrastructure to integrate into a single fluid system or secondary loop used to control the temperature of process equipment. It can achieve dynamic temperature control from -120℃ to 300℃.
Caratteristiche del prodotto
Parametri del prodotto
Modello | ZLF-35N ZLF-35NS ZLF-35NH ZLF-35NSH |
ZLF-50N ZLF-50NS ZLF-50NH ZLF-50NSH |
ZLF-80N ZLF-80NS ZLF-80NH ZLF-80NSH |
ZLF-125N ZLF-125NS ZLF-125NH ZLF-125NSH |
ZLF-200N ZLF-200NS ZLF-200NH ZLF-200NSH |
Intervallo di temperatura | -45-250 (the max Temp is determined by the heat and cold source supplied by the user)-40-135(The maximum temperature range can be operated by using glycol water formula solution) | ||||
ZLF-N | La fonte principale di freddo o la fonte principale di calore viene utilizzata per regolare il flusso del sistema attraverso un sistema di regolazione proporzionale e per controllare il calore del serraggio del serbatoio di reazione, mentre una serie di scambiatori di calore per il riscaldamento o il raffreddamento viene controllata o raffreddata. | ||||
ZLF-NS | Besides ZLF-N function, add one set heater used to reduce high temp | ||||
ZLF-NH | Besides ZLF-N function, add electrical heating function | ||||
ZLF-NSH | Oltre alla funzione ZLF- N, aggiungere un set di riscaldamento utilizzato per ridurre la temperatura elevata e la funzione di riscaldamento elettrico. | ||||
Area dello scambiatore di calore | 3.5㎡ | 5㎡ | 8㎡ | 12.5㎡ | 20㎡ |
Electric heatingfunction H | 25kW | 35kW | 50kW | 65kW | 80kW |
With 'H' has heating function | |||||
Modalità di controllo | Feed forward PiD + Our special dynamic control calculation, LNEYA PLC controller | ||||
Protocollo di comunicazione | MODBUS RTU protocol, RS485 interface, optional Ethemet interface/R232 interface | ||||
Selezione del controllo della temperatura | Controllo della temperatura di processo | ||||
Feedback della temperatura | The temp of three points: the inlet and outet of heat-conducing medium, material in reactor(External temp), PT100 sensor | ||||
Process temp feedback | Feedback sul processo della materia prima: PT100 o 4~20mA o comunicazione fornita | ||||
Temp accuracy | ±1℃ | ±1℃ | ±1℃ | ±1℃ | ±1℃ |
Pompa di circolazione | 150L/min 2,5BAR | 200L/min 2,5BAR | 400L/min 2,5BAR | 500L/min 2,5BAR | 750L/min 2,5BAR |
Ingresso e visualizzazione | Touch screen a colori da 7 pollici, visualizzazione del grafico della temperatura | ||||
Protezione di sicurezza | Self-diagnosis funcion;freezer overoad protecion; high pressure switch;, overload relay; themal protection device; high temp Protection and temp faut protecion | ||||
Eseguire il pezzo di valvola | Proportional control valve control signal 4-20mA | ||||
Materiale della custodia | SUS304 | ||||
Dimensioni del collegamento | DN40 | DN40 | DN50 | DN65 | DN80 |
Dimensioni cm | 150*120*185 | 180*120*210 | 180*120*210 | 225*120*240 | 225*120*240 |
Power AC380V 50HZ | 2.3kW | 3,5kW | 4,5kW | 8kW | 10.5kW |
With H power AC380V 50HZ | 27.3kW | 38.5kW | 54.5kW | 73kW | 90.5kW |
Shell materia | Cold rolled sheet (REL7035) |
Modello | SR-35N SR-35NS SR-35NH SR-35NSH |
SR-50N SR-50NS SR-50NH SR-50NSH |
SR-80N SR-80NS SR-80NH SR-80NSH |
SR-125N SR-125NS SR-125NH SR-125NSH |
SR-200N SR-200NS SR-200NH SR-200NSH |
Intervallo di temperatura | -120~250 (the max. Temp is determined by the heat and cold source supplied by the user)-40~135(The maximum temperature range can be operated by using glycol water formula solution) | ||||
SR-N | A set of cooling heat exchanger, heat exchanger, through proportional adjusting valve control cold heat into the heat exchanger, then through the uniform medium input to the reactor jacketed to do heat exchange and temp. Control, system has inside expansion tank |
||||
SR-NS | Besides SR- N function, add one set heater used to reduce high temp | ||||
SR-NH | Besides SR- N function, add electrical heating function | ||||
SR-NSH | Besides SR- N function, add one set heater used to reduce high temp and electrical heating function | ||||
Serbatoio di espansione | 100L | 200L | 280L | 390L | 500L |
Area dello scambiatore di calore | 3.5㎡ | 5㎡ | 8㎡ | 12.5㎡ | 20㎡ |
Electric heatingfunction H | 25kW | 35kW | 50kW | 65kW | 80kW |
With 'H' has heating function | |||||
Modalità di controllo | Feed forward PiD + Our special dynamic control calculation, LNEYA PLC controller | ||||
Protocollo di comunicazione | MODBUS RTU protocol, RS485 interface, optional Ethemet interface/R232 interface | ||||
Selezione del controllo della temperatura | Controllo della temperatura di processo | ||||
Feedback della temperatura | The temp of three points: the inlet and outet of heat-conducing medium, material in reactor(External temp), PT100 sensor | ||||
Process temp feedback | Feedback sul processo della materia prima: PT100 o 4~20mA o comunicazione fornita | ||||
Temp accuracy | ±1℃ | ±1℃ | ±1℃ | ±1℃ | ±1℃ |
Pompa di circolazione | 200L/min 2,5BAR | 250L/min 2,5BAR | 400L/min 2,5BAR | 500L/min 2,5BAR | 750L/min 2,5BAR |
Ingresso e visualizzazione | Touch screen a colori da 7 pollici, visualizzazione del grafico della temperatura | ||||
Protezione di sicurezza | Self-diagnosis funcion;freezer overoad protecion; high pressure switch;, overload relay; themal protection device; high temp Protection and temp faut protecion | ||||
Eseguire il pezzo di valvola | Proportional control valve control signal 4-20mA | ||||
Materiale della custodia | SUS304 | ||||
Dimensioni del collegamento | DN40 | DN40 | DN50 | DN65 | DN80 |
Dimensioni cm | 150*120*185 | 180*140*240 | 180*140*240 | 220*180*265 | 220*180*265 |
Power AC380V 50HZ | 2.3kW | 3,5kW | 4,5kW | 8kW | 10.5kW |
With H power AC380V 50HZ | 27.3kW | 38.5kW | 54.5kW | 73kW | 90.5kW |
Shell materia | Cold rolled sheet (REL7035) |
PRINCIPIO DI FUNZIONAMENTO
(Controllo della temperatura del materiale del reattore)
- Il metodo di modifica del valore impostato del controllo può rispondere al ritardo del sistema nel processo il più rapidamente possibile e ottenere una minore sovraelongazione del sistema. Il controllo è costituito da due serie di loop di controllo PID, denominati: loop principale e loop slave. L'uscita di controllo dell'anello principale viene utilizzata come valore impostato dell'anello slave. Controllando il gradiente di variazione della temperatura in questo modo, si garantisce l'accuratezza del controllo della temperatura del sistema.
- Il predittore di isteresi appositamente progettato genera un segnale dinamico yc(t) al posto della variabile di processo y(t) come segnale di retroazione. Generare un segnale e(t) per il controllore, in modo che il controllore preveda che l'azione di controllo non abbia un grande ritardo.

PER IL CONTROLLO DELLA TEMPERATURA DEI SISTEMI DI REATTORI
Un host controlla 5~60 reattori diversi
Sistema di controllo della temperatura senza contatto nella camicia del recipiente di reazione
Ogni reattore è controllato in modo indipendente e non influisce sugli altri.





Perché scegliere lneya come fornitore di controllo della temperatura?
Anni di esperienza
Clienti soddisfatti
m² Area di produzione
Tecnologie brevettate
Visita la fabbrica LNEYA
contattateci
Inviateci la vostra richiesta e vi contatteremo entro 24 ore.