Ricerca nell'intera stazione

SUNDI series Chiller and Heater Combo Units

Unità combinate di refrigerazione e riscaldamento della serie SUNDI

APPLICAZIONI

Dynamic constant temperature control of cold and hot sources of high-pressure reactors;

Dynamic constant temperature control of cold and hot sources of double-layer glass reactors;

Dynamic constant temperature control of cold and hot sources of double-layer reactors;

Constant temperature control of cold and hot sources of microchannel reactors;

Small constant temperature control systems, distillation system temperature control;

Low-temperature and high-temperature aging tests of materials;

Constant temperature control of combined chemical cold and hot sources;

Cooling and heating of semiconductor equipment;

Constant temperature control of refrigeration and heating of vacuum chambers.

 

 

Caratteristiche del prodotto

 

Modello SUNDI-320                SUNDI-320W
Intervallo di temperatura -30℃~180℃
Medium temp accuracy ±0.5℃

Precisione della temperatura del materiale

±1℃

Potenza di riscaldamento 2kW
Raffreddamento
capacità
180℃ 1,5kW
50℃ 1,5kW
0℃ 1,5kW
-5℃ 0.7kW
-15℃ 0.4kW
Flow、pressure max10L/min
0,8 bar
Refrigerante R-404A/R507C
Dimensioni del collegamento ZG1/2
Dimensioni cm 35*56*75
Peso kg 55 kg
Potenza AC 220V 50HZ 3.2kW(max)

 

 

Modello SUNDI-135
SUNDI-135W
SUNDI-155
SUNDI-155W
SUNDI-175
SUNDI-175W
SUNDI-1A10
SUNDI-1A10W
SUNDI-1A15
SUNDI-1A15W
Intervallo di temperatura  -10℃~+150℃
Modalità di controllo Feedback PID + il nostro speciale calcolo di controllo dinamico, controllore PLC
Temp control Modello di controllo della temperatura di processo e del rivestimento
Temp difference Impostare o controllare la differenza di temperatura tra l'olio del rivestimento e la materia prima.
Editor del programma 20 programs, each program can edit 40 steps
Communication Protoco Protocollo MODBUS RTU, interfaccia RS485
Material temp feedback PT100
Feedback della temperatura The temp of 3 points: the inlet and outlet of equipment,reactor material temperature(external temp. sensor)
Medium temp accuracy ±0.5℃
Precisione della temperatura del materiale ±1℃
Potenza di riscaldamento 3.5 5.5 7.5 10 15
Raffreddamento
capacità
150℃ 3.5 5.5 7.5 10 15
20℃ 3.5 5.5 7.5 10 15
-5℃ 2.1 3.3 4.2 6 9
Flow、pressure max
L/min bar
35 35 50 50 75
1 1 1.2 1.2 1.2
Compressore Highly / Panasonic / Emerson copeland / scroll compressor
Valvola di espansione Valvola di espansione elettronica
Evaporatore Scambiatore di calore a piastre
Pannello operativo Schermo tattile da 7 pollici, visualizzazione della curva di temperatura, uscita dati EXCEL
Protezione di sicurezza Self-diagnosis function; freezer overload protection; high pressure switch, overload relay,thermal protection device,
high temperature protection and temperature fault protection.
Sistema di circolazione chiuso L'intero sistema è a circolazione completamente chiusa, non c'è nebbia d'olio ad alta temperatura e non c'è vapore acqueo a bassa temperatura, la pressione non sale quando il sistema è in funzione. Il sistema fornisce automaticamente olio a bassa temperatura.
Refrigerante R-404A/R507C
Dimensioni del collegamento ZG3/4 ZG3/4 ZG1 ZG1 ZG1
Acqua di raffreddamento
@20℃
1300L/H
1,5bar~4bar
ZG1/2
1800L/H
1,5bar~4bar
ZG3/4
1800L/H
1,5bar~4bar
ZG3/4
2400L/H
1,5bar~4bar
ZG3/4
3600L/H
1,5bar~4bar
ZG1
Dimensioni cm 45*70*160 45*70*160 55*70*175 55*70*175 70*85*185
Peso kg 165 185 235 280 300
Potenza 380V 50HZ 6.7kW 9,5kW 12kW 15.5kW 23kW
Case materia Cold rolled steel powder coating (standard color 7035)
Opzionale Optional Ethernet interface and computer operation software configuration
Opzionale Outside touch screen display controller,
the communication line distance is 10 meter
OptionalPower 110V 50HZ single-phase, 110V 60HZ single-phase, 230V 60HZ single-phase, 220V 60HZ 3-phase, 440V~460V 60HZ 3-phase

 

Modello SUNDI-235
SUNDI-235W
SUNDI-255
SUNDI-255W
SUNDI-275
SUNDI-275W
SUNDI-2A10
SUNDI-2A10W
SUNDI-2A15
SUNDI-2A15W
SUNDI-2A25
SUNDI-2A25W
SUNDI-2A38W SUNDI-2A60W SUNDI-2A95W SUNDI-2A130W SUNDI-2A200W
Intervallo di temperatura -25℃~+200℃(can be -25℃~+300℃)
Modalità di controllo Feedback PID + il nostro speciale calcolo di controllo dinamico, controllore PLC
Temp control Modello di controllo della temperatura di processo e del rivestimento
Temp difference Impostare o controllare la differenza di temperatura tra l'olio del rivestimento e la materia prima.
Editor del programma 20 programs, each program can edit 40 steps
Communication Protoco Protocollo MODBUS RTU, interfaccia RS485
Material temp feedback PT100
Feedback della temperatura The temp of 3 points: the inlet and outlet of equipment,reactor material temperature(external temp. sensor)
Medium temp accuracy ±0.5℃
Precisione della temperatura del materiale ±1℃
Potenza di riscaldamento 3.5 5.5 7.5 10 15 25 38 60 95 130 200
Raffreddamento
capacità
200℃ 3.5 5.5 7.5 10 15 25 38 60 95 130 200
100℃ 3.5 5.5 7.5 10 15 25 38 60 95 130 200
50℃ 3.5 5.5 7.5 10 15 25 38 60 95 130 200
20℃ 3.5 5.5 7.5 10 15 25 38 60 95 130 200
-5℃ 3 4.5 6.3 8 11 19 30 46 70 80 125
-15℃ 1.8 2.8 3.8 4.6 7 12 16 22 32 43 65
Flow、pressure  max
L/min bar
35 35 50 60 110 150 200 250 400 400 600
1.2 1.2 1.2 1.2 1.5 1.5 1.5 2.5 2.5 2.5 2.5
Compressore Tecumseh Emerson copeland / Carlyle
Valvola di espansione Valvola di espansione elettronica
Evaporatore Scambiatore di calore a piastre
Pannello operativo Schermo tattile da 7 pollici, visualizzazione della curva di temperatura, uscita dati EXCEL
Protezione di sicurezza Self-diagnosis function; freezer overload protection; high pressure switch, overload relay,thermal protection device,
high temperature protection and temperature fault protection.
Sistema di circolazione chiuso L'intero sistema è a circolazione completamente chiusa, non c'è nebbia d'olio ad alta temperatura e non c'è vapore acqueo a bassa temperatura, la pressione non sale quando il sistema è in funzione. Il sistema fornisce automaticamente olio a bassa temperatura.
Refrigerante R-404A/R507C
Dimensioni del collegamento ZG3/4 ZG3/4 ZG1 ZG1 ZG1 DN32 DN40 DN50 DN65 DN65 DN80
Acqua di raffreddamento
@20℃
1500L/H
1,5bar~4bar
ZG1/2
1800L/H
1,5bar~4bar
ZG3/4
3000L/H
1,5bar~4bar
ZG3/4
4200L/H
1,5bar~4bar
ZG3/4
5400L/H
1,5bar~4bar
DN32
10m³/H
1,5bar~4bar
DN40
10m³/H
1,5bar~4bar
DN40
14m³/H
1,5bar~4bar
DN50
19m³/H
1,5bar~4bar
DN65
24m³/H
1,5bar~4bar
DN65
36m³/H
1,5bar~4bar
DN80
Dimensioni cm 45*70*160 45*70*160 55*70*175 65*85*185 70*85*185 80*120*185 150*100*185 200*145*205 200*145*205 250*145*225 300*160*225
Peso kg 165 185 230 280 300 550 750 1000 1250 1580 2150
Potenza 380V 50HZ 6.7kW 9,5kW 15kW 16kW 27kW 48kW 55kW 81kW 126kW 175kW 260kW
Case materia Cold rolled steel powder coating (standard color 7035)
Opzionale Optional Ethernet interface and computer operation software configuration
Opzionale Outside touch screen display controller,
the communication line distance is 10 meter
OptionalPower 110V 50HZ single-phase, 110V 60HZ single-phase, 230V 60HZ single-phase, 220V 60HZ 3-phase, 440V~460V 60HZ 3-phase
Opzionale SUNDI series can provide optional medium temperature control accuracy of ± 0.1 ℃ and material temperature control accuracy of ± 0.1 ℃ within a heating power of 25kW

 

Modello SUNDI-525
SUNDI-525W
SUNDI-535
SUNDI-535W
SUNDI-555
SUNDI-555W
SUNDI-575
SUNDI-575W
SUNDI-5A10
SUNDI-5A10W
SUNDI-5A15
SUNDI-5A15W
SUNDI-4A25
SUNDI-4A25W
SUNDI-4A38W SUNDI-4A60W SUNDI-4A95W SUNDI-4A130W SUNDI-4A200W
Intervallo di temperatura   -45℃~+250℃
Modalità di controllo Feedback PID + il nostro speciale calcolo di controllo dinamico, controllore PLC
Temp control Modello di controllo della temperatura di processo e del rivestimento
Temp difference Impostare o controllare la differenza di temperatura tra l'olio del rivestimento e la materia prima.
Editor del programma 20 programs, each program can edit 40 steps
Communication Protoco Protocollo MODBUS RTU, interfaccia RS485
Material temp feedback PT100
Feedback della temperatura The temp of 3 points: the inlet and outlet of equipment,reactor material temperature(external temp. sensor)
Medium temp accuracy ±0.5℃
Precisione della temperatura del materiale ±1℃
Potenza di riscaldamento 2.5 3.5 5.5 7.5 10 15 25 38 60 95 130 200
Capacità di raffreddamento 250℃ 2.5 3.5 5.5 7.5 10 15 25 38 60 95 130 200
100℃ 2.5 3.5 5.5 7.5 10 15 25 38 60 95 130 200
20℃ 2.5 3.5 5.5 7.5 10 15 25 38 60 95 130 200
0℃ 1.8 3 5 7 10 15 25 38 60 95 130 200
-20℃ 0.85 1.5 2.3 3.6 5 7.6 11 20 29 42 54 98
-35℃ 0.25 0.45 0.9 1.5 2 3.8 4.7 9 12 18 24 43
Flow、pressure max       L/min bar 20 35 35 50 60 110 150 200 250 400 400 600
1.2 1.2 1.2 1.2 1.5 1.5 1.5 1.5 2.5 2.5 2.5 2.5
Pompa di circolazione Pompa a trascinamento magnetico
Compressore Tecumseh/Emerson copeland/Carlyle
Valvola di espansione Valvola di espansione elettronica
Evaporatore Scambiatore di calore a piastre
Pannello operativo Schermo tattile da 7 pollici, visualizzazione della curva di temperatura, uscita dati EXCEL
Protezione di sicurezza Self-diagnosis function; freezer overload protection; high pressure switch, overload relay,thermal protection device,
high temperature protection and temperature fault protection.
Sistema di circolazione chiuso L'intero sistema è a circolazione completamente chiusa, non c'è nebbia d'olio ad alta temperatura e non c'è vapore acqueo a bassa temperatura, la pressione non sale quando il sistema è in funzione. Il sistema fornisce automaticamente olio a bassa temperatura.
Refrigerante R-404A/R507C
Dimensioni del collegamento ZG1/2 ZG3/4 ZG3/4 ZG3/4 ZG1 ZG1 DN32 DN50 DN50 DN65 DN65 DN65
Acqua di raffreddamento
@20℃
900L/H
1,5bar~4bar
ZG1/2
1400L/H
1,5bar~4bar
ZG1/2
1800L/H
1,5bar~4bar
ZG3/4
2400L/H
1,5bar~4bar
ZG3/4
3600L/H
1,5bar~4bar
ZG1
4800L/H
1,5bar~4bar
ZG1
9m³/H
1,5bar~4bar
DN40
10m³/H
1,5bar~4bar
DN50
15m³/H
1,5bar~4bar
DN50
20m³/H
1,5bar~4bar
DN65
32m³/H
1,5bar~4bar
DN80
46m³/H
1,5bar~4bar
DN100
Dimensioni cm 45*70*160 45*70*160 55*70*175 55*70*175 65*85*185 70*85*185 80*120*185 150*100*185 200*145*205 200*145*205 250*145*225 300*160*225
Peso kg 160 180 195 260 320 390 620 820 1100 1350 1680 2250
Power 380V 50hz AC220V 4kW 7kW 9kW 13kW 16kW 26kW 42kW 57kW 82kW 136 kW 183kW 309kW
Case materia Cold rolled steel powder coating (standard color 7035)
Opzionale Optional Ethernet interface and computer operation software configuration
Opzionale Outside touch screen display controller,
the communication line distance is 10 meter
OptionalPower 110V 50HZ single-phase, 110V 60HZ single-phase, 230V 60HZ single-phase, 220V 60HZ 3-phase, 440V~460V 60HZ 3-phase
Opzionale SUNDI series can provide optional medium temperature control accuracy of ± 0.1 ℃ and material temperature control accuracy of ± 0.1 ℃ within a heating power of 25kW

 

Modello SUNDI-625
SUNDI-625W
SUNDI-635
SUNDI-635W
SUNDI-655
SUNDI-655W
SUNDI-675
SUNDI-675W
SUNDI-6A10
SUNDI-6A10W
SUNDI-6A15W SUNDI-6A25W SUNDI-6A38W SUNDI-6A60W
Intervallo di temperatura  -60℃~+250℃
Modalità di controllo Feedback PID + il nostro speciale calcolo di controllo dinamico, controllore PLC
Temp control Modello di controllo della temperatura di processo e del rivestimento
Temp difference Impostare o controllare la differenza di temperatura tra l'olio del rivestimento e la materia prima.
Editor del programma 20 programs, each program can edit 40 steps
Communication Protoco Protocollo MODBUS RTU, interfaccia RS485
Material temp feedback PT100
Feedback della temperatura The temp of 3 points: the inlet and outlet of equipment,reactor material temperature(external temp. sensor)
Medium temp accuracy ±0.5℃
Precisione della temperatura del materiale ±1℃
Potenza di riscaldamento 2.5 3.5 5.5 7.5 10 15 25 38 60
Capacità di raffreddamento 250℃ 2.5 3.5 5.5 7.5 10 15 25 38 60
100℃ 2.5 3.5 5.5 7.5 10 15 25 38 60
20℃ 2.5 3.5 5.5 7.5 10 15 25 38 60
-40℃ 0.95 1.45 2.3 3.1 4.8 7.8 18 23 31
-55℃ 0.25 0.5 0.75 0.9 1.5 2.8 6 8 11
Flow、pressuremax  L/min bar 20 35 35 50 60 110 150 200 250
1.2 1.2 1.2 1.2 1.5 1.5 1.5 1.5 2.5
Pompa di circolazione Pompa a trascinamento magnetico
Compressore Tecumseh/Emerson copeland/Carlyle
Valvola di espansione Valvola di espansione elettronica
Evaporatore Scambiatore di calore a piastre
Pannello operativo Schermo tattile da 7 pollici, visualizzazione della curva di temperatura, uscita dati EXCEL
Protezione di sicurezza Self-diagnosis function; freezer overload protection; high pressure switch, overload relay,thermal protection device,
high temperature protection and temperature fault protection.
Sistema di circolazione chiuso L'intero sistema è a circolazione completamente chiusa, non c'è nebbia d'olio ad alta temperatura e non c'è vapore acqueo a bassa temperatura, la pressione non sale quando il sistema è in funzione. Il sistema fornisce automaticamente olio a bassa temperatura.
Refrigerante R-404A/R23
Dimensioni del collegamento ZG1/2 ZG3/4 ZG3/4 ZG1 ZG1 ZG1 DN32 DN40 DN50
Acqua di raffreddamento
@20℃
1100L/H
1,5bar~4bar
ZG1/2
2000L/H
1,5bar~4bar
ZG3/4
2300L/H
1,5bar~4bar
ZG3/4
2600L/H
1,5bar~4bar
ZG3/4
3300L/H
1,5bar~4bar
ZG1
4000L/H
1,5bar~4bar
ZG1 1/4
8,5 m³/H
1,5bar~4bar
DN40
14m³/H
1,5bar~4bar
DN50
20m³/H
1,5bar~4bar
DN65
Dimensioni cm 55*70*175 55*70*175 55*70*175 65*85*185 65*85*185 80*120*185 150*100*185 200*145*205 200*145*205
Peso kg 205 225 300 340 380 380 980 1350 1580
Potenza 380V 50HZ 5kW 10kW 12kW 18kW 22kW 28kW 56kW 73kW 110kW
Case materia Cold rolled steel powder coating (standard color 7035)
Opzionale Optional Ethernet interface and computer operation software configuration
Opzionale Outside touch screen display controller,
the communication line distance is 10 meter
OptionalPower 110V 50HZ single-phase, 110V 60HZ single-phase, 230V 60HZ single-phase, 220V 60HZ 3-phase, 440V~460V 60HZ 3-phase
Opzionale SUNDI series can provide optional medium temperature control accuracy of ± 0.1 ℃ and material temperature control accuracy of ± 0.1 ℃ within a heating power of 25kW

 

Modello SUNDI-825W SUNDI-835W SUNDI-855W SUNDI-875W SUNDI-8A10W SUNDI-8A15W SUNDI-8A25W SUNDI-8A38W SUNDI-8A60W SUNDI-8A80W
Intervallo di temperatura  -80℃~+250℃
Modalità di controllo Feedback PID + il nostro speciale calcolo di controllo dinamico, controllore PLC
Temp control The material temperature control and equipment outlet temperature control modes can be freely selected
Temp difference Impostare o controllare la differenza di temperatura tra l'olio del rivestimento e la materia prima.
Editor del programma 20 programs, each program can edit 40 steps
Communication Protoco Protocollo MODBUS RTU, interfaccia RS485
Material temp feedback PT100
Feedback della temperatura The temp of 3 points: the inlet and outlet of equipment,reactor material temperature(external temp. sensor)
Medium temp accuracy ±0.5℃
Precisione della temperatura del materiale ±1℃
Potenza di riscaldamento 3 3.5 5.5 7.5 10 15 25 38 60 80
Capacità di raffreddamento 250℃ 2.5 3.5 5.5 7.5 10 15 25 38 60 80
20℃ 2.5 3.5 5.5 7.5 10 15 25 38 60 80
-60℃ 1 1.4 1.6 3 3.5 5.8 10 16 23 32
-75℃ 0.3 0.42 0.7 1.3 1.5 2.4 5 8 11 16
Flow、pressuremax
L/min bar
20 35 35 50 60 110 150 250 400 400
1.2 1.2 1.2 1.2 1.5 1.5 1.5 1.5 2.5 2.5
Pompa di circolazione Pompa a trascinamento magnetico
Compressore Emerson copeland/Carlyle
Valvola di espansione Valvola di espansione elettronica
Evaporatore Scambiatore di calore a piastre
Pannello operativo Schermo tattile da 7 pollici, visualizzazione della curva di temperatura, uscita dati EXCEL
Protezione di sicurezza Self-diagnosis function; freezer overload protection; high pressure switch, overload relay,thermal protection device,
high temperature protection and temperature fault protection.
Sistema di circolazione chiuso L'intero sistema è a circolazione completamente chiusa, non c'è nebbia d'olio ad alta temperatura e non c'è vapore acqueo a bassa temperatura, la pressione non sale quando il sistema è in funzione. Il sistema fornisce automaticamente olio a bassa temperatura.
Refrigerante R-404A/R508B
Dimensioni del collegamento ZG1/2 ZG3/4 ZG3/4 ZG1 ZG1 ZG1 DN32 DN40 DN65 DN65
Acqua di raffreddamento
@20℃
1800L/H
1,5bar~4bar
ZG3/4
2000L/H
1,5bar~4bar
ZG3/4
2800L/H
1,5bar~4bar
ZG3/4
3500L/H
1,5bar~4bar
ZG1
4200L/H
1,5bar~4bar
ZG1
5600L/H
1,5bar~4bar
DN32
10m³/H
1,5bar~4bar
DN40
18m³/H
1,5bar~4bar
DN65
28m³/H
1,5bar~4bar
DN80
30m³/H
1,5bar~4bar
DN80
Dimensioni cm 55*70*175 55*70*175 65*85*185 70*85*185 70*85*185 80*120*185 150*100*185 200*145*205 245*170*225 300*160*225
Peso kg 240 285 345 500 600 950 1300 1550 2200 2850
Potenza 380V 50HZ 9,5kW 11kW 17kW 20kW 26kW 36kW 59kW 98kW 135kW 177kW
Case materia Cold rolled steel powder coating (standard color 7035)
Opzionale Optional Ethernet interface and computer operation software configuration
Opzionale Outside touch screen display controller,
the communication line distance is 10 meter
OptionalPower 110V 50HZ single-phase, 110V 60HZ single-phase, 230V 60HZ single-phase, 220V 60HZ 3-phase, 440V~460V 60HZ 3-phase
Opzionale SUNDI series can provide optional medium temperature control accuracy of ± 0.1 ℃ and material temperature control accuracy of ± 0.1 ℃ within a heating power of 25kW

 

Modello SUNDI-955W SUNDI-975W SUNDI-9A10W SUNDI-9A15W SUNDI-9A25W SUNDI-9A38W SUNDI-9A60W SUNDI-9A80W
Intervallo di temperatura   -90℃~+250℃
Modalità di controllo Feedback PID + il nostro speciale calcolo di controllo dinamico, controllore PLC
Temp control Modello di controllo della temperatura di processo e del rivestimento
Temp difference Impostare o controllare la differenza di temperatura tra l'olio del rivestimento e la materia prima.
Editor del programma 20 programs, each program can edit 40 steps
Communication Protoco Protocollo MODBUS RTU, interfaccia RS485
Material temp feedback PT100
Feedback della temperatura The temp of 3 points: the inlet and outlet of equipment,reactor material temperature(external temp. sensor)
Medium temp accuracy ±0.5℃
Precisione della temperatura del materiale ±1℃
Potenza di riscaldamento 5.5 7.5 10 15 25 38 60 80
Capacità di raffreddamento 250℃ 5.5 7.5 10 15 25 38 60 80
0℃ 5.5 7.5 10 15 25 38 60 80
-60℃ 2.8 3.2 4.2 6 10 16 24 32
-80℃ 0.8 1.2 1.6 2.1 3.5 6 11 15
-85℃ 0.5 0.7 0.85 1.3 1.9 3.5 6 8
Flow、pressure max
L/min bar
35 50 60 110 150 250 400 400
1.2 1.2 1.5 1.5 1.5 1.5 2.5 2.5
Pompa di circolazione Pompa a trascinamento magnetico
Compressore Emerson copeland/Carlyle
Valvola di espansione Valvola di espansione elettronica
Evaporatore Scambiatore di calore a piastre
Pannello operativo Schermo tattile da 7 pollici, visualizzazione della curva di temperatura, uscita dati EXCEL
Protezione di sicurezza Self-diagnosis function; freezer overload protection; high pressure switch, overload relay,thermal protection device,
high temperature protection and temperature fault protection.
Sistema di circolazione chiuso L'intero sistema è a circolazione completamente chiusa, non c'è nebbia d'olio ad alta temperatura e non c'è vapore acqueo a bassa temperatura, la pressione non sale quando il sistema è in funzione. Il sistema fornisce automaticamente olio a bassa temperatura.
Refrigerante R-404A/R508B
Dimensioni del collegamento ZG3/4 ZG1 ZG1 ZG1 DN32 PN10 DN40 PN10 DN65 PN10 DN65 PN10
Acqua di raffreddamento
@20℃
3400L/H
1,5bar~4bar
ZG1
4500L/H
1,5bar~4bar
ZG1
5200L/H
1,5bar~4bar
ZG1 1/4
8m³/H
1,5bar~4bar
DN40
12m³/H
1,5bar~4bar
DN50
20m³/H
1,5bar~4bar
DN65
30m³/H
1,5bar~4bar
DN80
40m³/H
1,5bar~4bar
DN100
Dimensioni cm 80*120*185 80*120*185 80*120*185 150*100*185 200*145*205 200*145*205 250*160*225 300*160*225
Peso kg 365 570 680 950 1400 1750 2400 3150
Potenza 380V 50HZ 16kW 27kW 30kW 42kW 59kW 83kW 130kW 188kW
Case materia Cold rolled steel powder coating (standard color 7035)
Opzionale Optional Ethernet interface and computer operation software configuration
Opzionale Outside touch screen display controller,
the communication line distance is 10 meter
OptionalPower 110V 50HZ single-phase, 110V 60HZ single-phase, 230V 60HZ single-phase, 220V 60HZ 3-phase, 440V~460V 60HZ 3-phase
Opzionale SUNDI series can provide optional medium temperature control accuracy of ± 0.1 ℃ and material temperature control accuracy of ± 0.1 ℃ within a heating power of 25kW

 

Modello SUNDI-1055W SUNDI-1075W SUNDI-10A10W SUNDI-10A15W SUNDI-10A25W SUNDI-10A38W SUNDI-10A60W SUNDI-10A80W
Intervallo di temperatura   -100℃~+100℃
Modalità di controllo Feedback PID + il nostro speciale calcolo di controllo dinamico, controllore PLC
Temp control Modello di controllo della temperatura di processo e del rivestimento
Temp difference Impostare o controllare la differenza di temperatura tra l'olio del rivestimento e la materia prima.
Editor del programma 20 programs, each program can edit 40 steps
Communication Protoco Protocollo MODBUS RTU, interfaccia RS485
Material temp feedback PT100
Feedback della temperatura The temp of 3 points: the inlet and outlet of equipment,reactor material temperature(external temp. sensor)
Medium temp accuracy ±0.5℃
Precisione della temperatura del materiale ±1℃
Potenza di riscaldamento 5.5 7.5 10 15 25 38 60 80
Capacità di raffreddamento 100℃ 5.5 7.5 10 15 25 38 60 80
0℃ 5.5 7.5 10 15 25 38 60 80
-80℃ 2.8 3.4 4.1 5 8 13 22 30
-90℃ 1.2 1.6 2 3 4.8 7.5 12 16
 -95℃ 0.7 0.9 1.2 1.8 2.9 4.5 7.2 9.5
Flow、pressure max
L/min bar
35 50 60 110 150 250 400 400
1.2 1.2 1.5 1.5 1.5 1.5 2.5 2.5
Pompa di circolazione Pompa a trascinamento magnetico
Compressore Emerson copeland/Carlyle
Valvola di espansione Valvola di espansione elettronica
Evaporatore Scambiatore di calore a piastre
Pannello operativo Schermo tattile da 7 pollici, visualizzazione della curva di temperatura, uscita dati EXCEL
Protezione di sicurezza Self-diagnosis function; freezer overload protection; high pressure switch, overload relay,thermal protection device,
high temperature protection and temperature fault protection.
Sistema di circolazione chiuso L'intero sistema è a circolazione completamente chiusa, non c'è nebbia d'olio ad alta temperatura e non c'è vapore acqueo a bassa temperatura, la pressione non sale quando il sistema è in funzione. Il sistema fornisce automaticamente olio a bassa temperatura.
Refrigerante R-404A/R23/R14
Dimensioni del collegamento ZG3/4 ZG1 ZG1 DN32 DN32 DN40 DN65 DN65
Acqua di raffreddamento
@20℃
5000L/H
1.5~4bar
ZG1 1/4
7000L/H
1.5~4bar
DN40
9000L/H
1.5~4bar
DN40
12m³/H
1.5~4bar
DN50
20m³/H
1.5~4bar
DN65
25m³/H
1.5~4bar
DN65
40m³/H
1.5~4bar
DN80
50m³/H
1.5~4bar
DN100
Dimensioni cm 80*120*185 150*100*185 150*100*185 200*145*205 200*145*205 250*160*225 300*160*225 400*160*225
Peso kg 565 705 890 1250 1600 2100 2950 3350
Potenza 380V 50HZ 26W 28kW 37kW 49kW 69kW 82kW 170kW 200kW
Case materia Cold rolled steel powder coating (standard color 7035)
Opzionale Optional Ethernet interface and computer operation software configuration
Opzionale Outside touch screen display controller,
the communication line distance is 10 meter
Potenza opzionale 110V 50HZ single-phase, 110V 60HZ single-phase, 230V 60HZ single-phase, 220V 60HZ 3-phase, 440V~460V 60HZ 3-phase
Opzionale SUNDI series can provide optional medium temperature control accuracy of ± 0.1 ℃ and material temperature control accuracy of ± 0.1 ℃ within a heating power of 25kW

La tecnologia di raffreddamento ad altissima temperatura può raffreddare direttamente da una temperatura elevata di 300℃[perché solo il mezzo di trasferimento del calore nella camera di espansione entra in contatto con l'ossigeno dell'aria (e la temperatura del serbatoio di espansione è compresa tra la temperatura normale e 60℃), il che può ridurre il rischio di ossidazione del mezzo di trasferimento del calore e di assorbimento di acqua nell'aria. Ad alta temperatura, il mezzo di conduzione del calore non evapora e il controllo continuo della temperatura di - 80℃ ~ 190℃, - 70℃ ~ 220℃, - 88℃ ~ 170℃, - 55℃ ~ 250℃ e - 30℃ ~ 300℃ può essere realizzato senza pressurizzazione.

1. Visualizza tutti i tipi di temperature di controllo del processo.
2. Indica il livello del liquido del fluido termovettore nel vaso di espansione.
3. Mostra l'indicazione del funzionamento del sistema di refrigerazione.
4. Mostra l'indicazione del funzionamento del riscaldatore.
5. Indica il funzionamento della pompa di circolazione.
6. Visualizza il controllo della temperatura (modello di controllo della temperatura dei materiali, controllo della temperatura media di conduzione del calore).
7. È possibile impostare il controllo del limite superiore e inferiore della temperatura.
8. È possibile impostare la differenza di temperatura tra la camicia e il materiale del reattore.
9. Mostra l'allarme per aggiungere il liquido quando è vuoto.
10. Il compressore di refrigerazione può essere impostato per funzionare manualmente o automaticamente.

Nuovi materiali | Controllo della temperatura di produzione dei gas speciali

Soluzione per il controllo della temperatura di produzione intermedia API

Soluzione di controllo della temperatura della concentrazione di distillazione

Per saperne di più

Per saperne di più


Dalla nostra fondazione nel 2006abbiamo servito oltre 30.000 clienti e detiene diversi brevetti che dimostrano la nostra innovazione e affidabilità. I nostri refrigeratori sono selezionati per oltre 100 università progetti di laboratorio in tutto il mondo ed esportati in oltre 20 paesi. Garantiamo la massima qualità attraverso un rigoroso 3 fasi processo di controllo della qualità: ispezione visiva, test delle prestazioni e test di sicurezza elettrica. Il nostro impegno per l'eccellenza è ulteriormente supportato dal nostro Cliente 24/7 impegno per l'assistenza. Inoltre, abbiamo agenti negli Stati Uniti, in Canada, Australia, Russia e Corea del Sud, che ci rendono un partner globale e fidato per le vostre esigenze di refrigerazione. Scegliete lneya per la qualità e il supporto al vostro progetto.
18+

Anni di esperienza

30000+

Clienti soddisfatti

25000

m² Area di produzione

80+

Tecnologie brevettate

*
*
Invio....
Inviato con successo!
Invio fallito! Riprovare più tardi
Errore e-mail!
Errore telefonico!