Quali sono i refrigeranti per il congelatore a bassissima temperatura a 120 gradi?
I refrigeranti dei diversi produttori di congelatori a bassissima temperatura sono diversi. I refrigeranti comunemente utilizzati nelle apparecchiature di refrigerazione LNEYA sono R404, R22, ecc. Qual è la differenza tra i due refrigeranti a bassissima temperatura (120 gradi)?
Since the saturation pressure of R404A is higher than R22, the design pressure of the pressure vessel in the system should be changed to ensure safety. Such as liquid storage and gas-liquid separators. At the same time, the set values of the safety valve and fusible plug installed on the system components will also change. Since the gas density of R404A is about 50% larger than that of R22 under the same exhaust gas amount, the pipe diameter selected is larger than R22 when piping design using R404A refrigerant.
For the same compressor, the current of the R40A in the -120 degree ultra-low temperature freezer is greater than R22, so the wire diameter of the AC contactor, thermal relay and cable of the compressor should be adjusted. In terms of system protection, the high pressure switch setting is adjusted from the original 2.45 MPa to 2.7 MPa. The exhaust pressure of the R404A refrigerant is about 1.2 times that of R22, and the mass flow rate is about 1.5 times that of R22. The exhaust flow rate increases and the resistance increases. In general, the heat transfer capacity of the condenser is increased by 20% to 30% compared to R22.
The saturation pressure of R404A and R22 is different at the same temperature, so the action mechanism of the -120 degree ultra-low temperature freezer R404A thermal expansion valve is different from that of R22. At the same time, because the R404A refrigerant and lubricating oil have different compatibility with the sealing material, the expansion valve sealing material should also be changed accordingly. Therefore, the R404A special expansion valve should be selected in the selection of the thermal expansion valve. Since the saturation pressure of 404A is different from that of R22, the air tightness test pressure is greater than R22. At the same time, the vacuum degree of the system is higher than R22, and the water content is lower than R22. The refrigerant should be charged in liquid form during charging to prevent changes in the R404A configuration.
The refrigerant R404A used in the 120 degree ultra-low temperature freezer is a non-azeotropic mixture. The concentration of the non-azeotropic mixture changes with temperature and pressure, which brings certain difficulties to the production, commissioning and maintenance of the refrigeration system. The heat transfer performance of the system will also have a certain impact, especially when the refrigerant leaks, the system refrigerant needs to be completely drained and replaced, so as to ensure the proportion of each mixed component, and also achieve the design cooling effect, otherwise it will get worse. .
The refrigerant of the -120 degree ultra-low temperature freezer should be selected according to the corresponding equipment. LNEYA selects the corresponding environmentally friendly refrigerant refrigerant, which is more in line with the development of the environmental protection theme of the contemporary era.

Raccomandazioni correlate
-
The advantages of water cooled chiller you need to know
1144Industrialchillers can be generally divided into water-cooled and air-cooled according tothe type of refrigeration. The heat exchange medium of Water Cooled Chillers iswater.LNEYA has designed and developed a new type of temperature controlequ...
Visualizza i dettagli -
La necessità di un ciclo di riscaldamento e raffreddamento della temperatura nel processo di idrogenazione catalitica
1111In recent years, with the rising price of oil, the demand for benzene obtained from coking benzene has increased, coupled with the country's increasing emphasis on environmental protection, the widespread application of coking benzene hydrogenatio...
Visualizza i dettagli -
Destructive application effect of components in chip temperature measuring device
977The components can be tested in high-temperature and low-temperature cold sources in the microfluidic chip temperature measuring device. The destructive analysis of components is also an important application, which can measure the design, structu...
Visualizza i dettagli -
Advantages of bearing cryogenic treatment equipment
1119One of the names of the ultra-low temperature freezer is the bearing cryogenic treatment equipment. Wuxi Guanya LNEYA's ultra-low temperature freezer is designed for large volume ratio; large capacity bearing capacity design; can set the temperatu...
Visualizza i dettagli