Multi-stage refrigeration system centrifugal compressor repair instructions
After the centrifugal compressor of the cascade refrigeration system is disassembled, the dimensions of each journal (cooperating with the impeller, bearing, coupling, etc.) are measured with an outer diameter micrometer to calculate the roundness and cylindricity deviation. The value should be Within the allowable range. When the tolerance is large, check if the straightness deviation of the spindle is too large. Place the spindle in the casing or place it on the top of the lathe so that the spindle is in a free state. Use a dial gauge to measure the radial runout of the spindle journal.
The centrifugal compressor of the cascade refrigeration system is divided into 4-8 equal parts, and the rotor is driven according to the direction of rotation of the rotor. The large value of the dial gauge swing is the radial circle runout value. At the same time, the straightness deviation of the main shaft is measured at the appropriate position of the main shaft with two dial gauges, and the radial runout value should be no more than 0.01mm. If the over-standard is too large, the main shaft should be replaced.
Check the surface of the journal of the centrifugal compressor of the cascade refrigeration system for scratches, grooves, scratches, grinding points, etc. If necessary, perform flaw detection. Small defects can be scraped and polished by hand; large defects It can be repaired by surfacing, electroplating, spraying, etc., and then ground and polished. When the flaw detection reveals cracks or serious defects, it is generally not repaired and replaced.
At the same time, the end face runout of the centrifugal compressor impeller of the cascade refrigeration system should be measured, and the value should be within the allowable range. If the value of the end face jump exceeds the allowable range value, when the over-standard is small, the repair is generally not performed. When the value is large, the assembly relationship between the impeller and the main shaft can be adjusted by the method of adding the gasket. The impeller should be dynamically balanced and statically balanced after the overhaul. test.

The parts and fittings of the centrifugal compressor of the cascade refrigeration system have the specified technical standards and requirements for use. In the absence of reliable basis, it is necessary to strictly abide by these standards and never lower the standard.
The cascade refrigeration system should have a fixed maintenance and repair plan, carefully learn the correct understanding and use of equipment requirements by the user, and timely cooperate with the on-site user for regular maintenance.
Raccomandazioni correlate
-
Influenza dei fattori di refrigerazione sui refrigeratori industriali antideflagranti chiusi ad alta temperatura
1086Check whether the high and low temperature enclosed explosion-proof industrial chiller is the cause of its own failure. The selection must be accurate. If the model is not in place, the required refrigeration effect will also not be achieved. It i...
Visualizza i dettagli -
Failure Analysis of Ultra Low Temperature Chiller Supporting Distillation Equipment
1306Once the freezer used in the matching distillation equipment fails, we need to solve it in a timely and effective manner to avoid affecting the operation of the entire experiment. In the pharmaceutical, chemical and other industries, low temperatu...
Visualizza i dettagli -
Buone notizie! Wuxi Guanya LNEYA Refrigeration ha un nuovo nome
2551According to the `` Notice on Publishing the Evaluation Results of Unicorn and Gazelle Enterprises in the 2019 South Jiangsu National Independent Innovation Demonstration Zone '' issued by Jiangsu Sunan National Independent Innovation Demonstratio...
Visualizza i dettagli -
Where do you need low temperature chiller and introduction
869Even though water is one of the most precious and scarce resources, it is still used as a coolant in many laboratories. Unfortunately, most of the water used as a coolant is not recycled, resulting in higher and higher laboratory costs and wasted ...
Visualizza i dettagli