FL-WS 5℃~30℃
High power chiller- Cooling Power89kW~1724kW
- Power Supply3N/380V/50Hz
- Weight850kG~7900kG
Product data download
Product Description
1.The standard design conditions are: chilled water:outlet water temperature 7 ° C, return water temperature 12 ° C; condensing temperature 40 ° C.
2.Due to continuous updating of product technology, the above data is subject to change without prior notice.
3.In addition to the listed product models, our company can customize non-standard units according to customer requirements.

This series of equipment is suitable for various production process cold sources in the fields of chemical industry, medicine, machinery, etc. It can provide -110℃~30℃ refrigeration medium, and can be used as ice storage, low-temperature air supply and other process cold sources required by production processes. Our company can specially design the unit according to the requirements of users. The unit adopts advanced semi-enclosed screw compressor, which is low-carbon, energy-saving and environmentally friendly; it has good performance and low noise, and can run without trouble for more than 100,000 hours; the temperature control can be step-by-step energy regulation or stepless energy regulation control. According to the heat load required by the specific production, the outlet water temperature of the refrigerant is used as the control point, and the control center sends instructions to adjust the movement of the energy regulation slide valve to adjust the load of the compressor unit to achieve a real energy-saving effect.
Model FL- | 100WS | 200WS | 300WS | 400WS | 510WS | 660WS | 1700WD | |
Cooling capacity 5℃ |
kW | 103 | 203 | 280 | 370 | 506 | 678 | 1724 |
Kcal/hr*10³ | 89 | 175 | 241 | 318 | 435 | 583 | 1483 | |
±0.5 | ||||||||
Power Supply | 3N/380V/50HZ | |||||||
Cooling input power | 23 | 46 | 62 | 81 | 110 | 146 | 362 | |
Compressor | Form | Semi-hermetic screw compressor | ||||||
Energy control range | 0~25~37.5~50~62.5~75~87.5~100(12.5% segment control) | |||||||
Chilled Water | Form | Dry, flooded or falling film heat exchangers | ||||||
Chilled water volume T/H | 20 | 35 | 50 | 65 | 86 | 115 | 280 | |
Water pressure drop KPa | 40~80 | |||||||
Take over specifications | DN65 | DN100 | DN125 | |||||
Cooling water | Form | Horizontal shell and tube | ||||||
Cooling water volume T/H | 22 | 45 | 60 | 80 | 110 | 140 | 360 | |
Water pressure drop KPa | 40~80 | |||||||
Take over specifications | DN65 | DN100 | DN125 | |||||
Protective Device | High and low voltage protection, anti-icing, heat release protection, safety valve, overload protection, phase loss, reverse phase, undervoltage, overvoltage, water flow protection, etc. | |||||||
Refrigerant | Filling amount Kg | 22 | 44 | 55 | 58 | 80 | 115 | 235 |
Dimensions | Length mm | 250 | 264 | 313 | 314 | 314 | 328 | 397 |
Width mm | 85 | 90 | 110 | 110 | 110 | 110 | 160 | |
High mm | 130 | 143 | 157 | 178 | 180 | 202 | 225 | |
Weight | 850 | 1270 | 1740 | 2480 | 2870 | 3400 | 7900 | |
Operating Weight | 900 | 1420 | 1890 | 2580 | 3120 | 3700 | 8600 |
You may also be interested in these products
LT -45℃~30℃
LOW TEMPERATURE COOLING CIRCULATOR For fast liquid cooling 1. Can use ethylene glycol mixed with water for circulating refrigeration, saving resources 2.Circulating pipeline design, prolong t…
LT 10℃~30℃
Saving water resources & circulating cooling 1. Can use ethylene glycol mixed with water for circulating refrigeration, saving resources 2.Circulating pipeline design, prolong the use time of circulating …
LT -25℃~30℃
Rapid refrigeration using imported brand semi-enclosed piston compressor, semi-enclosed piston two-stage compressor, semi-enclosed screw compressor 1. Can use ethylene glycol mixed …
loading…