SEARCH

KRYCH-15/15W

KRYCH-15/15W

Battery testing chamber/Industrial covers for power battery test
  • Temperture Control-45℃~100℃
  • Antifreeze Flow2~20L/min
  • Cooling Power for chamber1.2kW~6kW
  • Cooling Power for Antifreeze1.2kW~7.5kW
  • Source Power23kW

Product data download

Configuration Details

Model KRYCH-15W
KRYCH-15
Temperature control -40℃~135℃ Antifreeze -45℃~100℃ Test Chamber
Antifreeze flow 2L/min~20L/min    ±0.2L/min
Antifreeze pressure Measure and display the inlet and outlet pressure and display the pressure on the touch screen
Test chamber volume cm 100*100*100   1m3
Heating Power 7.5kW Antifreeze 5kW Test Chamber

Antifreeze

Cooling Power

135℃ 7.5kW
20℃ 7.5kW
0℃ 7.5kW
-20℃ 4.5kW
-30℃ 2.5kW
-35℃ 1.8kW

Test Chamber

Cooling Power

100℃ 6kW
-20℃ 3.5kW
-40℃ 1.2kW

Antifreeze

Temperature accuracy

±0.3℃

Test Chamber

Temperature accuracy

±0.3℃
Circulating air inside the test chamber 3500m3/h
When the door is opened, the internal circulation fan is automatically turned off, and the door will be displayed on the touch screen.
Controller PLC controller, fuzzy PID control algorithm
Letter of agreement Ethernet interface TCP/IP protocol
Temperature Feedback Internal temperature of equipment tank, condensing temperature of refrigeration system, compressor suction temperature, cooling water temperature (water cooling type)
Heating Refers to the maximum heating output power of the system (according to each model)
The heater has triple protection and an independent temperature limiter to ensure the safety of the heating system
Heating power of 15kW adopts voltage regulator, and heating power output control adopts 4~20mA linear control
Cooling capacity It means that it has the ability to take away heat at different temperatures (under ideal conditions). The actual working condition needs to consider the heat dissipation of the environment. Please enlarge it appropriately and take insulation measures.
High temperature cooling module Can cool the module from high temperature 150℃
Circulation pump flow, pressure Using LNEYA magnetic drive pump
Source 380V50HZ 23kW max
Weight cm 125*235*190 Excluding external protrusions Air-cooled and water-cooled in the same size
Compressor Emerson Copeland Scroll Flexible Compressors
Evaporator Plate heat exchanger
Refrigeration accessories Emerson/Danfoss brand filter drier, oil separator, etc.
Throttling mode Electronic expansion valve
Operation panel 7-inch color touch screen, temperature curve display\EXCEL data export
Security It has self-diagnosis function; phase sequence and phase failure protector, refrigerator overload protection; high pressure pressure switch, overload relay, thermal protection device and other safety protection functions.
Refrigerant R-404A/R507C
Antifreeze interface ZG3/4 and switch valve
Water-cooled W Models with W are water-cooled
Water cooled condenser Tube heat exchanger
Cooling water 32℃ 6m³/H
Shell Material Plastic spraying of cold-rolled sheet (standard color 7035)

Product Description

  1. Adopt the upper and lower double-layer box design, the box contains antifreeze battery cooling system, the control and test systems of the two boxes are completely independent operation;
  2. The box door and the pressure relief port are equipped with explosion-proof chains;
  3. The stainless steel full welding design is adopted in the box, which can meet the storage requirements of 0.5m fire water
  4. The insulation layer of the box body is designed to be 100mm thick, and it is composed of insulation materials with low thermal conductivity and high temperature resistant materials, which can meet the long-term high and low temperature impact requirements from -40 degrees to 100 degrees;
  5. Each box is equipped with an explosion-proof pressure relief port, which automatically releases pressure when overpressure is sensed;
  6. The refrigeration system of this device adopts frequency conversion control, combined with hot gas and electric heating control algorithm to operate efficiently, saving more than 20% of energy.

The integrated system provides high temperature, low temperature, flow and pressure control requirements for new energy power battery samples.

The double-layer high and low temperature box is used for high and low temperature test devices for power battery samples. It is currently mainly used in the new energy battery industry. It can directly complete high and low temperature charge and discharge for battery cells or modules, PACK in the test box, or high and low temperature storage, etc. Function, under the condition of test battery failure, an explosion-proof pressure relief and fire-fighting device is added.

Click online message to inquire about product details
Inquiry about the test chamber KRYCH series
*
*
Submitting…
Successfully submitted!
Submission failed! Please try again later
Email error!
Phone error!

You may also be interested in these products

loading…

已经是到最后一篇内容了!

Expand more!
Leave a Message